For the case that one of the limit frequency parameters (p5282 or p5283) is written and the
current blocking frequency of the band-stop filter is beyond the relevant new limit frequency, the
following applies:
● If the adaptation is active, the band-stop filter is automatically set to the relevant limit
frequency when p5282 or p5283 is written.
● If the adaptation is not active, the band-stop filter is automatically set to the relevant limit
frequency when the adaptation is activated.
5.9.3.3

Remedy for insufficient adaptation

If the adaptation does not change the blocking frequency of the adapted current setpoint filter
during operation, then the mechanical resonant frequency is not sufficiently excited and
therefore has no negative effect on the operation. If you nevertheless want to change the
behavior of the adaptation, the following options are available:
● Change the activation threshold (p5284).
● Change the blocking frequency in the relevant filter parameters in order to obtain a different
start value for the adaptation.
● Increase the speed controller gain via p1460 or p5272 to further excite the mechanical
resonant frequency. However, observe the stability of the control loop with this setting.
5.9.4

Function diagrams and parameters

Overview of important faults (see SINAMICS S120/S150 List Manual)
● F07419
Overview of important parameters (see SINAMICS S120/S150 List Manual)
● p0108[0...n]
● p1400[0...n]
● p5271[0...n]
● p5272[0...n]
● p5273[0...n]
● r5274
● p5275[0...n]
● r5276
● r5277
● p5280[0...n]
● p5281[0...n]
● p5282[0...n]
● p5283[0...n]
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
Drive: Incorrect current setpoint filter adaptation
Drive object function module
Speed control configuration
Online / One Button Tuning configuration
Online tuning dynamic response factor
Online tuning load dynamic response factor
CO: Online / One Button Tuning dynamic response estimated
Online / One Button Tuning dynamic response time constant
Online / One Button Tuning Kv factor estimated
Online / One Button Tuning precontrol symmetrizing time estimated
Current setpoint filter adaptation configuration
Current setpoint filter adaptation assignment
Current setpoint filter adaptation lower limit frequency
Current setpoint filter adaptation upper limit frequency
Servo control
5.9 Autotuning
125