Advertisement

Basic functions
8.26 Upgrade the firmware and project
Once the project has been downloaded or automatic configuration has been carried out, the
firmware is automatically upgraded on all the connected DRIVE-CLiQ components. This
upgrades all DRIVE-CLiQ components to the firmware releases that match the memory card.
Update
This operation can take several minutes. This is indicated by the RDY-LED on the
corresponding components flashing green/red and the Control Unit RDY-LED flashing orange
at 0.5 Hz.
Parameter p7827 indicates the progress.
The update has been completed if the RDY-LED on the Control Unit stops to flash at 0.5 Hz.
Once the update process has been completed, the RDY-LED of the respective component
goes into a steady light condition, for which the upgrade has been completed and the new
firmware has been activated. For the components for which the RDY LED flashes green/red at
2 Hz you must perform a POWER ON to activate the new firmware.
Note
When activating the new firmware, it is possible that a component interrupts cyclic
communication. Communication problems will then occur that you must acknowledge.
For individual components, use the "General" Startdrive diagnostics screen to read out the
firmware version. The versions of the DRIVE-CLiQ components and that of the Control Unit can
also differ. Information can be found in the version overview.
Note
DRIVE-CLiQ components with higher firmware releases are downwards compatible and also
operate with DRIVE-CLiQ components that have lower firmware releases.
Note
Upgrade for SINAMICS S120 Chassis
Upgrading S120 Chassis devices is more complex and involves more settings than for
Booksize devices. You can find a detailed description of the procedure when upgrading
Chassis devices at the following SIEMENS internet site Upgrading S120 Chassis.
support.industry.siemens.com/cs/ww/en/view/60494864)
8.26.1

Updating the firmware and STARTER project data using the web server

Function description
Using the web server, you can upgrade or downgrade the firmware – and load existing
STARTER project data to your drive. A firmware and existing STARTER project data can be
loaded to the drive, either simultaneously or at different instants in time.