7.4

Resonance damping

Function description
The resonance damping function dampens active current oscillations that can occur under no-
load conditions. Resonance damping is active in a range between 5% and 90% of the rated
motor frequency (p0310), but only up to 45 Hz.
Note
Maximum frequency resonance damping
When p1349 = 0, the changeover limit is automatically set to 95% of the rated motor frequency,
but only up to a maximum of 45 Hz.
The following figure shows the signal curve of the function.
Function diagrams (see SINAMICS S120/S150 List Manual)
● 6310
Overview of important parameters (see SINAMICS S120/S150 List Manual)
● r0066
● r0078
● p0310[0...n]
● p1338[0...n]
● p1339[0...n]
● p1349[0...n]
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
Vector control - Resonance damping and slip compensation
CO: Output frequency
CO: Torque-generating actual current value
Rated motor frequency
U/f mode resonance damping gain
U/f mode resonance damping filter time constant
Maximum frequency
U/f control (vector control)
7.4 Resonance damping
301