Quick Stop In The Event Of A Power Failure Or Emergency Stop (Servo) - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

12.4

Quick stop in the event of a power failure or emergency stop (servo)

A drive line-up generally responds when the power fails with an OFF2, even when a Control
Supply Module and a Braking Module is being used. This means that the connected motors
coast down. The Control Supply Module provides the electronics with power via the supply
system or DC link. In this way, controlled movements can be made if a power failure occurs
provided that the DC link voltage is still available. The following section describes how all the
drives carry out a quick stop (OFF3) if the power fails.
Figure 12-5
Example: interconnection of quick stop due to power failure or emergency off
In addition to the component wiring shown above, each drive object that is to carry out a quick
stop if the power fails needs to be parameterized. If parameterization is not carried out, the drive
coasts down once a DC link undervoltage has been identified (OFF2). To implement the OFF3
function (quick stop), the following parameters need to be set:
● p1240 = 5 (activates Vdc_min monitoring)
As well as the DC link monitor, which is always active, this activates another variable alarm
threshold, which should be set to a value above the undervoltage shutdown threshold of
360 V ±2 % in p1248.
● p1248 ≤ 570 V (for Active Line Modules)
p1248 ≤ 510 V (for Smart Line Modules)
This alarm level (in volts) indicates that the set value has been fallen below. Fault F07403
is triggered when this threshold is reached.
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
12.4 Quick stop in the event of a power failure or emergency stop (servo)
Applications
699

Advertisement

Table of Contents
loading

Table of Contents