Basic information about the drive system
14.12 System rules, sampling times and DRIVE-CLiQ wiring
● The connection to the Control Unit is obtained from the PROFIBUS address of the CX/NX
(10 → X100, 11 → X101, 12 → X102, 13 → X103, 14 → X104, 15 → X105).
● It is not permitted to combine SIMOTION Master Control Units and SINUMERIK Slave
Control Units.
● It is not permitted to combine SINUMERIK Master Control Units and SIMOTION Slave
Control Units.
14.12.5.2

Recommended interconnection rules

The following recommended rules should be observed for the DRIVE-CLiQ wiring:
General
● The following applies to all DRIVE-CLiQ components with the exception of the Control Unit:
The DRIVE-CLiQ sockets Xx00 are DRIVE-CLiQ inputs (Uplink), the other DRIVE-CLiQ
sockets are outputs (Downlink).
– The DRIVE-CLiQ cable from the Control Unit should be connected to DRIVE-CLiQ
– The DRIVE-CLiQ connections between the power units should each be connected from
Line Modules
● A single Line Module should be connected directly to the Control Unit (recommended
DRIVE-CLiQ socket: X100).
– Several Line Modules should be connected in series.
– For Active Line Modules of the Chassis-2 format with more than 4 modules connected in
Motor Modules
● No more than 6 Motor Modules should be connected to a DRIVE-CLiQ line on the Control
Unit (including with vector, U/f control).
● Motor Modules should be connected directly to the Control Unit in vector control.
– If DRIVE-CLiQ socket X100 is already assigned to a Line Module, DRIVE-CLiQ socket
– Several Motor Modules should be connected in a line.
– For Motor Modules of the Chassis-2 format with more than 4 modules connected in
● In servo control, Motor Modules should be connected to a DRIVE-CLiQ line together with
the Line Module.
– Several Motor Modules should be connected in a line.
– If there is already a Line Module present, the first Motor Module should be connected in
– If there is no Line Module present, the first Motor Module should be connected directly
848
socket X200 on the first Booksize power unit or X400 on the first Chassis power unit.
the DRIVE-CLiQ sockets X201 to X200 and/or X401 to X400 on the follow-on
component.
parallel, the X101 port is also to be used in order to wire modules 4 through n.
X101 should be used.
parallel, the X101 port is also to be used in order to wire modules 4 through n.
line to socket X201 of the Line Module.
to the Control Unit (recommended DRIVE-CLiQ socket: X100).
Function Manual, 06/2019, 6SL3097-5AB00-0BP2