8.12 Armature short-circuit
8.12.1

Internal armature short-circuit braking

Overview
With the "Internal armature short-circuit braking" function, the motor windings are short-
circuited via a Motor Module.
Supported Motor Modules
The function has been released for Motor Modules in the Booksize and Chassis formats.
Requirement
● Short-circuit-proof motors (p0320 < p0323)
● One of the following motor types is used:
– rotating permanent-magnet synchronous motor (p0300 = 2xx)
– linear permanent-magnet synchronous motor (p0300 = 4xx)
● The maximum current of the Motor Module (r0209.0) must be at least 1.8x the motor short-
circuit current (r0331).
Note
Internal short-circuit braking despite power failure
If armature short-circuit braking should still be maintained despite a power failure, you must
buffer the 24 V power supply for the Motor Module. For this purpose, you can use for
example a dedicated SITOP unit for the Motor Module or a Control Supply Module (CSM).
Configuring the function
Carry out the following steps to configure the function:
Setting the function
The internal armature short-circuit braking is set with p1231 = 4.
Activating the function
The function is activated and initiated if the signal source of p1230 is set to a "1" signal.
Deactivating the function
The function is deactivated if the signal source of p1230 is set to a "0" signal. When triggered
by a fault, the fault must have been removed and acknowledged.