Procedure
1. Connect the line contactor control contact to DI/DO 8
Note
Pay attention to the continuous current-carrying capacity of the digital output (see
SINAMICS S120 Equipment Manual for Control Units and Additional System Components).
If necessary, use an auxiliary contactor!
2. Parameterize DI/DO 8 as an output (p0728.8 = 1).
3. Assign parameter p0738 the control signal for the line contactor r0863.1
4. Connect the line contactor feedback contact to DI/DO 9.
5. Assign p0860 with input signal r0722.9.
6. Enter the monitoring time for the line contactor (100 ms) in p0861.
Function diagrams (see SINAMICS S120/S150 List Manual)
● 8938
Overview of important parameters (see SINAMICS S120/S150 List Manual)
● p0860
● r0863.0...2
● p0867
● p0869
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
Active Infeed - Missing enables, line contactor control
BI: Line contactor, feedback signal
CO/BO: Drive coupling status word / control word
Power section main contactor hold time after OFF1
Configuration sequence control
Infeed
3.4 Line contactor control