8.22 Parking axis / parking encoder
Example: Parking axis
In the following example, an axis is parked. To ensure that the axis parking is effective, the drive
must be brought to a standstill (e.g. via STW1.0 (OFF1). All components assigned to the motor
control (e.g. power unit and motor encoder) are shut down.
Figure 8-9
Parking an encoder
When an encoder is parked, the encoder being addressed is switched to inactive (r0146 = 0).
● Control is carried out via the encoder control/status words of the cyclic telegram
(Gn_STW.14 and Gn_ZSW.14).
● With a parked motor measuring system, the associated drive must be brought to a standstill
by the higher-level control system (disable pulses e.g. via STW1.0/OFF1).
● The monitoring functions for the power unit remain active (r0126 = 1).
Note
Removing/replacing parked components
Once parked components have been disconnected/connected, they can only be unparked
once they have been successfully integrated in the actual topology (see r7853).
386
Flow diagram: parking axis
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
Drive functions