● Direct setpoint specification / MDI for positioning and setting up
● Reference point approach
● Stop responses due to alarms
Jerk limitation is not active when messages are generated with stop responses OFF1/OFF2/
OFF3.
9.8.2.5

Starting against a closed brake

Function description
Under EPOS, if the drive should start against a closed brake, for example, for a suspended
load, then the enable signal p0899.2 is briefly withdrawn. The drive pulses are canceled and
fault F07490 is output.
To avoid this happening, using p1513 activate a supplementary torque which corresponds to
the brake holding torque. As a result, after releasing the brake, the load cannot sag and the
drive remains in closed-loop control without fault F07490 being output.
9.8.2.6

Function diagrams and parameters

Function diagrams (see SINAMICS S120/S150 List Manual)
● 3630 EPOS - Traversing range limits (r0108.4 = 1)
Overview of important parameters (see SINAMICS S120/S150 List Manual)
● p2571
● p2572
● p2573
● p2646
Software limit switch
● p2578
● p2579
● p2580
● p2581
● p2582
● r2683.0...14
STOP cam
● p2568
● p2569
● p2570
● r2684.0...15
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
EPOS maximum speed
EPOS maximum acceleration
EPOS maximum delay
CI: EPOS velocity override
CI: EPOS software limit switch, minus signal source
CI: EPOS software limit switch, plus signal source
CO: EPOS software limit switch, minus
CO: EPOS software limit switch, plus
BI: EPOS software limit switch activation
CO/BO: EPOS status word 1
BI: EPOS STOP cam activation
BI: EPOS STOP cam, minus
BI: EPOS STOP cam, plus
CO/BO: EPOS status word 2
Function modules
9.8 Basic positioner
473