Note
Operation of motors in the field-weakening range
If the motors are to be operated in the field-weakening range > 2:1, the value of parameter
p2000 must be set ≤ 1/2 x maximum speed of the drive object.
Scaling for the A_INF drive object
Table 8-3
Size
Reference frequency
Reference voltage
Reference current
Reference power
Reference modulation
depth
Reference temperature
Reference electrical an‐
gle
Scaling for the S_INF drive object
Table 8-4
Size
Reference frequency
Reference voltage
Reference current
Reference power
Reference modulation
depth
Reference temperature
Reference electrical an‐
gle
Scaling for the B_INF drive object
Table 8-5
Size
Reference frequency
Reference voltage
Reference current
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
Scaling for the A_INF drive object
Scaling parameter
100% = p2000
100% = p2001
100% = p2002
100% = r2004
100% = Maximum output
voltage without overload
100 % = p2006
100 % = p2005
Scaling for the S_INF drive object
Scaling parameter
100% = p2000
100% = p2001
100% = p2002
100% = r2004
100% = Maximum output
voltage without overload
100 % = p2006
100 % = p2005
Scaling for the B_INF drive object
Scaling parameter
100% = p2000
100% = p2001
100% = p2002
8.2 Reference parameters/scaling
Default when commissioning for the first time
p2000 = p0211
p2001 = p0210
p2002 = r0206/p0210/√3
r2004 = r0206
-
100°C
90°
Default when commissioning for the first time
p2000 = 50 Hz
p2001 = p0210
p2002 = r0206/p0210/√3
r2004 = r0206
-
100°C
90°
Default when commissioning for the first time
p2000 = 50 Hz
p2001 = p0210
p2002 = r0206/p0210/√3
Basic functions
311