Fault 47: Overtemp Bulb – Current Too High
InfoCenter Display:
Fault Description
This fault is reported when the overtemp bulb circuit is drawing too much current from the TEC-5001 controller.
Note:
The overtemp bulb may also be referred to as the high water temperature indicator light.
Circuit Description
One output from the primary TEC controller drives the overtemp indicator bulb.
Recommended Service Actions
Step 1: Verify that the fault repeats.
1.
Clear the system faults from the InfoCenter. Refer to
2.
Operate the machine.
Pass
The fault did not repeat. Go to
Note:
If the fault does not repeat, an isolated event has occurred.
Fail
The fault repeated. Go to Step 2.
Step 2: Test the output circuit for a short.
1.
Open up the operator console as needed, and remove the warning lamp assembly
____FAULT
#47____
WARN
- OVER
Clearing Faults from the InfoCenter (page
Returning the Machine to Service (page 21)
147
19).
and follow the steps listed.
(Figure
84).