SmartLogger1000
User Manual
No.
Parameter
4
Reactive
power output
at night
5
Strong
adaptability
Power
6
quality
optimization
mode
Issue 12 (2019-01-15)
Description
In some specific application
scenarios, a power grid
company requires that the
inverter can perform reactive
power compensation at night to
ensure that the power factor of
the local power grid meets
requirements.
If the value of power grid short
circuit capacity/power plant
installed capacity is less than 3
and the power grid impedance
exceeds the upper threshold, the
power grid quality will be
affected and the inverter may be
unable to run properly. Set
Strong adaptability to Enable.
If Power quality optimization
mode is set to Enable, the
inverter output current
harmonics will be optimized.