Huawei SmartLogger1000 User Manual page 203

Hide thumbs Also See for SmartLogger1000:
Table of Contents

Advertisement

SmartLogger1000
User Manual
No.
Parameter
76
Voltage rise
suppression
active
derating
point
Feature Parameters
Table 7-8 Parameter description
No.
Parameter
1
LVRT
2
LVRT
threshold
Issue 12 (2019-01-15)
Description
The Japanese standard
requires that the inverter
should derate the active
power to prevent the grid
voltage from rising when
the output voltage
exceeds a certain value.
Description
When the power grid
voltage is abnormally low
for a short time, the
inverter cannot disconnect
from the power grid
immediately and has to
work for some time. This is
called LVRT.
Specifies the threshold for
triggering LVRT.
Copyright © Huawei Technologies Co., Ltd.
Unit
Value Range
V
109.0 V, 109.5 V, 110.0
V, 110.5 V, 111.0 V,
111.5 V, 112.0 V, 112.5
V, 113.0 V, 113.5 V,
114.0 V, and 114.5 V
Unit
Value Range
N/A
Disable
Enable
V
[50%Vn, 92%Vn]
7 WebUI
Remarks
The parameter
value is
automatically
displayed after
Voltage rise
suppression
reactive
adjustment
point is set.
The value of
Voltage rise
suppression
active derating
point must be
greater than that
of Voltage rise
suppression
reactive
adjustment
point.
Remarks
This parameter is set to
Enable by default if
the German
BDEW-MV grid code
is selected.
This parameter is
displayed when LVRT
is set to Enable.
In 1000 V inverters,
the
SUN2000-(8KTL-28K
TL) does not support
this parameter.
Vn represents the rated
voltage.
190