Protection Parameters
Table 7-7 Parameter description
No.
Parameter
1
Unbalance
voltage
protection
2
Phase
protection
point
Phase angle
3
offset
protection
10 minute
4
OV
protection
5
10 minute
OV
protection
time
Level-1 OV
6
protection
7
Level-1 OV
protection
time
8
Level-2 OV
protection
9
Level-2 OV
protection
time
Issue 12 (2019-01-15)
Description
Specifies the inverter
protection threshold in
the case of unbalanced
power grid voltage.
The Japanese standard
requires that during
passive islanding
detection, protection
should be triggered if an
abrupt voltage phase
change is detected.
The standards of certain
countries and regions
require that the inverter
needs to be protected
when the three-phase
angle offset of the power
grid exceeds a certain
value.
Specifies the 10-minute
overvoltage protection
threshold.
Specifies the 10-minute
overvoltage protection
duration.
Specifies the level-1
overvoltage protection
threshold.
Specifies the level-1
overvoltage protection
duration.
Specifies the level-2
overvoltage protection
threshold.
Specifies the level-2
overvoltage protection
duration.
Copyright © Huawei Technologies Co., Ltd.
Unit
Value Range
%
[0.0, 50.0]
º
[3, 15]
N/A
Disable
Enable
V
[1 x Vn, 1.36 x Vn]
ms
1000 V inverter:
[50, 600000]
Others: [50, 7200000]
V
[1 x Vn, 1.36 x Vn]
ms
1000 V inverter:
[50, 600000]
Others: [50, 7200000]
V
SUN2000-65KTL-C1
/70KTL-C1: [1 x
Vn, 1.5 x Vn]
Others: [1 x Vn, 1.36
x Vn]
ms
1000 V inverter:
[50, 600000]
Others: [50, 7200000]
7 WebUI
Remarks
N/A
Configurable
abruptly changed
phase angles are 3° ,
6° , 9° , 12° , and 15° ,
which are displayed
after the Japanese
grid code is
selected.
N/A
Vn represents the
rated voltage.
Vn represents the
rated voltage.
Vn represents the
rated voltage.
183