Parameter
Soft start time
Soft start time after
grid failure
2.
Parameter
Plant active power
gradient
Active power change
gradient
3.
4.
Issue 12 (2019-01-15)
Description
Specifies the duration for the
power to gradually increase when
the inverter starts.
Specifies the time for the power to
gradually increase when the
inverter restarts after the power
grid recovers.
Log in as Special User, choose Monitoring > SUN2000 > Running Param. >
Adjustment, and set the following parameters.
Description
Adjusts the rate of active power
rise due to light changes.
Adjusts the change speed of the
inverter active power.
Log in as Special User and choose Settings > Active power control. Ensure that Active
power control is set to Disable.
Log in as Special User and choose Settings > Export Limitation.
Figure 7-68 Setting export limitation parameters
Copyright © Huawei Technologies Co., Ltd.
7 WebUI
Recommended Value
20
20
Recommended Value
0
125%/s
If the maximum value is
50%/s, set this parameter to
50%/s.
242