Running parameters
Figure 7-22 Running parameters
SN list
Figure 7-23 SN list
Issue 12 (2019-01-15)
Baud rate is set to 115200 by default, which provides optimal communications performance and
does not need to be changed.
If Anti-crosstalk is set to Enable, the inverter with a PLC STA in the SN list can access networking.
Parameters Box-type transformer No. and Winding No. can be set for the PLC CCO with
SUN2000 V100R001C72SPC100 or later versions. In multi-split transformer scenarios, specify
Winding No. based on the actual winding number of the SmartLogger connected to the transformer.
When the box-type transformer and winding numbers of the inverter with an STA are consistent with
those of the PLC CCO, the inverter can access networking.
The SN list displays the relevant information of the inverters with PLC STAs that can be connected.
Tap Synchronize, and synchronize the box-type transformer and winding numbers of the PLC CCO
to the inverter.