Device Management; Connecting Devices - Huawei SmartLogger1000 User Manual

Hide thumbs Also See for SmartLogger1000:
Table of Contents

Advertisement

SmartLogger1000
User Manual

7.11.8 Device Management

7.11.8.1 Connecting Devices

Because of permission restriction, log in as Advanced User or Special User. Choose
Maintenance > Connect Device to access the target page.
Figure 7-77 Connecting devices
Issue 12 (2019-01-15)
Ensure that the extension of the license file to be imported is .dat or .zip.
Huawei devices can be automatically detected or manually added. The EMI, power meter, slave
SmartLogger, and third-party devices cannot be automatically detected. You need to add them
manually.
Before manually adding an EMI connected over the COM port, set RS485 parameters correctly by
following the instructions in
Type to EMI. After adding an EMI manually, correctly set the EMI parameters. For details, see
7.8.4.2 Setting EMI
Parameters.
Before manually adding the Modbus or DL/T645 power meter, set RS485 parameters correctly by
following the instructions in
Modbus power meter, correctly set the power meter parameters. For details, see
Power Meter
Parameters. When adding a power meter, set Device Type to Power Meter and
Comm.protocal to the protocol supported by the power meter.
When manually adding a slave SmartLogger, correctly set Modbus TCP parameters. Set Link
setting to Enable, and set the client IP address to the IP address for the slave SmartLogger. For
details, see
7.10.2.5 Setting Modbus TCP
Type to SmartLogger and set IP Address to the IP address of the slave SmartLogger.
When connecting a third-party device, you need to import a configuration file for the device and
then manually add the device.
An accessed device can be removed manually, and a removed device can be added again.
Copyright © Huawei Technologies Co., Ltd.
7.10.2.2 Setting RS485
Parameters. When adding an EMI, set Device
7.10.2.2 Setting RS485
Parameters. Before manually adding the
Parameters. When adding a slave SmartLogger, set Device
7 WebUI
7.10.2.3 Setting
249

Advertisement

Table of Contents
loading

Table of Contents