3.4 Determining the Installation Position

Before installing the SmartLogger, determine an appropriate position to ensure that the
SmartLogger works properly.
Comply with the following requirements when determining the installation position for the
SmartLogger:
Issue 12 (2019-01-15)
Do not install the SmartLogger outdoors because it is protected to IP20.
Install the SmartLogger in a dry environment to protect it against water.
Keep the product in an ambient temperature range of –40° C to +60° C and away from
direct sunlight.
The communication distance for the RS485 port should be less than 1000 m and for the
Ethernet less than 100 m.
Install the SmartLogger at an appropriate height for the user's ease to view and operate
on the monitoring panel.
Do not place the SmartLogger upside down. Ensure that the heat dissipation holes are
facing upwards, preventing dust from entering the SmartLogger and reducing its service
life.
Choose appropriate installation method and position for the Smart Logger according to
its weight and size. For details, refer to
If you install the SmartLogger on a wall or along a guide rail, the area for connecting
cables should be downwards.
The SmartLogger is at least 100 mm away from the neighboring objects on both sides,
the top side, and the bottom side respectively, as shown in