04
05
06
07
p10040
SI TM54F F-DI input mode / SI F-DI inp_mode
TM54F_MA,
Can be changed: C2(95)
TM54F_SL
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Sets the input mode for the safety digital inputs (F-DI).
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
Note:
Only an NC contact can be connected for the safety digital inputs not listed.
p10041
SI TM54F F-DI enable for test / SI F-DI enab test
TM54F_MA,
Can be changed: C2(95)
TM54F_SL
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Enable signal for the integration of F-DI in the test (forced checking procedure) of the sensor power supply.
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
Note:
F-DI: Failsafe Digital Input
p10042[0...5]
SI TM54F F-DO 0 signal sources / SI F-DO 0 S_src
TM54F_MA,
Can be changed: C2(95)
TM54F_SL
Data type: Integer16
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the signal sources for F-DO 0.
The 6 signal sources in p10042[0...5] are AND'ed and the result is output at F-DO 0.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
SLS_active
SDI_pos_active
SDI_neg_active
SLP_active
Signal name
F-DI 0, DI 1+ (X521.3)
F-DI 1, DI 3+ (X521.5)
F-DI 2, DI 5+ (X522.2)
F-DI 3, DI 7+ (X522.4)
F-DI 4, DI 9+ (X522.6)
F-DI 5, DI 11+ (X531.3)
F-DI 6, DI 13+ (X531.5)
F-DI 7, DI 15+ (X532.2)
F-DI 8, DI 17+ (X532.4)
F-DI 9, DI 19+ (X532.6)
Signal name
F-DI 0, power supply L1+
F-DI 1, power supply L1+
F-DI 2, power supply L1+
F-DI 3, power supply L1+
F-DI 4, power supply L1+
F-DI 5, power supply L2+
F-DI 6, power supply L2+
F-DI 7, power supply L2+
F-DI 8, power supply L2+
F-DI 9, power supply L2+
Selected
Selected
Selected
Selected
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
NO contact
NO contact
NO contact
NO contact
NO contact
NO contact
NO contact
NO contact
NO contact
NO contact
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Test active
Test active
Test active
Test active
Test active
Test active
Test active
Test active
Test active
Test active
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
783
2 Parameters
2.2 List of parameters
Not selected
Not selected
Not selected
Not selected
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 0000 0000 0000 bin
0 signal
NC contact
NC contact
NC contact
NC contact
NC contact
NC contact
NC contact
NC contact
NC contact
NC contact
Access level: 3
Func. diagram: 2848
Unit selection: -
Expert list: 1
Factory setting
0000 0000 0000 0000 bin
0 signal
No test
No test
No test
No test
No test
No test
No test
No test
No test
No test
Access level: 3
Func. diagram: 2857
Unit selection: -
Expert list: 1
Factory setting
0
-
-
-
-
FP
2850
2850
2850
2850
2850
2851
2851
2851
2851
2851
FP
-
-
-
-
-
-
-
-
-
-
983