Bi: Binector-Connector Converter Status Word 5 / Bin/Con Zsw5; Invert Binector-Connector Converter Status Word / Bin/Con Zsw Inv - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
[14] = Bit 14
[15] = Bit 15
Dependency:
Refer to: p2088, r2089
p2084[0...15]

BI: Binector-connector converter status word 5 / Bin/con ZSW5

B_INF, CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Unsigned32 / Binary
CU_G150_DP,
P-Group: Communications
CU_G150_PN, ENC,
Not for motor type: -
TB30, TM150, TM31,
VECTOR_G
Min
-
Description:
Selects bits to be sent to the PROFIdrive controller.
The individual bits are combined to form free status word 5.
Index:
[0] = Bit 0
[1] = Bit 1
[2] = Bit 2
[3] = Bit 3
[4] = Bit 4
[5] = Bit 5
[6] = Bit 6
[7] = Bit 7
[8] = Bit 8
[9] = Bit 9
[10] = Bit 10
[11] = Bit 11
[12] = Bit 12
[13] = Bit 13
[14] = Bit 14
[15] = Bit 15
Dependency:
Refer to: p2088, r2089
p2088[0...4]

Invert binector-connector converter status word / Bin/con ZSW inv

B_INF, CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Unsigned16
CU_G150_DP,
P-Group: Communications
CU_G150_PN, ENC,
Not for motor type: -
TB30, TM150, TM31,
VECTOR_G
Min
-
Description:
Setting to invert the individual binector inputs of the binector connector converter.
Index:
[0] = Status word 1
[1] = Status word 2
[2] = Free status word 3
[3] = Free status word 4
[4] = Free status word 5
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
496
Signal name
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Inverted
Inverted
Inverted
Inverted
Inverted
Inverted
Inverted
Inverted
Inverted
Inverted
Inverted
Inverted
Inverted
Inverted
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 2472
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2472
Unit selection: -
Expert list: 1
Factory setting
0000 0000 0000 0000 bin
0 signal
Not inverted
Not inverted
Not inverted
Not inverted
Not inverted
Not inverted
Not inverted
Not inverted
Not inverted
Not inverted
Not inverted
Not inverted
Not inverted
Not inverted
SINAMICS G130/G150
FP
-
-
-
-
-
-
-
-
-
-
-
-
-
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents