Zero Mark Selection Input Terminal / Zm_Sel Inp_Term - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

p0493

Zero mark selection input terminal / ZM_sel inp_term

ENC
Can be changed: U, T
Data type: Integer16
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Sets the input terminal for selecting the reference mark via BERO/switching signal when performing referencing with
several zero marks.
The encoder interface supplies the position of the reference mark, which was detected immediately after the positive
edge of the BERO signal.
Value:
0:
1:
2:
3:
4:
5:
6:
7:
8:
Notice:
For CX32, NX10 and NX15, only DI/DO 9, 10, 11 can be selected as fast inputs (refer to the Equipment Manual).
To the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note:
Refer to the encoder interface for PROFIdrive.
The terminal must be set as input (p0728).
For p0493 = 0 (factory setting) the following applies:
- there is no logic operation between the reference mark search and an input signal.
For p0493 > 0, the following applies:
- the positive edge of the input signal is evaluated. If the negative edge is to be evaluated, signal inversion must be
parameterized via p0490.
- if a parameter change is rejected, a check should be performed as to whether the input terminal is already being
used in p0580, p0680, p2517, or p2518.
p0493[0...n]
Zero mark selection input terminal / ZM_sel inp_term
VECTOR_G
Can be changed: U, T
Data type: Integer16
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Sets the input terminal for selecting the reference mark via BERO/switching signal when performing referencing with
several zero marks.
The encoder interface supplies the position of the reference mark, which was detected immediately after the positive
edge of the BERO signal.
Value:
0:
1:
2:
3:
4:
5:
6:
7:
8:
Notice:
For CX32, NX10 and NX15, only DI/DO 9, 10, 11 can be selected as fast inputs (refer to the Equipment Manual).
To the terminal designation:
The first designation is valid for CU320, the second for CU310.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
No selection via BERO
DI/DO 9 (X122.10/X121.8)
DI/DO 10 (X122.12/X121.10)
DI/DO 11 (X122.13/X121.11)
DI/DO 13 (X132.10/X131.2)
DI/DO 14 (X132.12/X131.4)
DI/DO 15 (X132.13/X131.5)
DI/DO 8 (X122.9/X121.7)
DI/DO 12 (X132.9/X131.1)
No selection via BERO
DI/DO 9 (X122.10/X121.8)
DI/DO 10 (X122.12/X121.10)
DI/DO 11 (X122.13/X121.11)
DI/DO 13 (X132.10/X131.2)
DI/DO 14 (X132.12/X131.4)
DI/DO 15 (X132.13/X131.5)
DI/DO 8 (X122.9/X121.7)
DI/DO 12 (X132.9/X131.1)
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
8
Calculated: -
Dyn. index: EDS, p0140
Units group: -
Scaling: -
Max
8
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
199