p8942[0...3]

CBE2x Default Gateway of Station / CBE2x Def Gateway

CU_G130_DP
Can be changed: U, T
(PROFINET CBE20),
Data type: Unsigned8
CU_G130_PN
P-Group: -
(PROFINET CBE20),
Not for motor type: -
CU_G150_DP
(PROFINET CBE20),
Min
CU_G150_PN
0
(PROFINET CBE20)
Description:
Sets the standard gateway for the Communication Board Ethernet 20/25 (CBE20/CBE25).
Dependency:
Refer to: p8940, p8941, p8943, p8944, p8945
Note:
The interface configuration (p8940 and following) is activated with p8945.
The parameter is not influenced by setting the factory setting.
p8943[0...3]

CBE2x Subnet Mask of Station / CBE2x Subnet Mask

CU_G130_DP
Can be changed: U, T
(PROFINET CBE20),
Data type: Unsigned8
CU_G130_PN
P-Group: -
(PROFINET CBE20),
Not for motor type: -
CU_G150_DP
(PROFINET CBE20),
Min
CU_G150_PN
0
(PROFINET CBE20)
Description:
Sets the subnet mask for the Communication Board Ethernet 20/25 (CBE20/CBE25).
Dependency:
Refer to: p8940, p8941, p8942, p8944, p8945
Note:
The interface configuration (p8940 and following) is activated with p8945.
The parameter is not influenced by setting the factory setting.
p8944

CBE2x DHCP Mode / CBE2x DHCP Mode

CU_G130_DP
Can be changed: U, T
(PROFINET CBE20),
Data type: Unsigned8
CU_G130_PN
P-Group: -
(PROFINET CBE20),
Not for motor type: -
CU_G150_DP
(PROFINET CBE20),
Min
CU_G150_PN
0
(PROFINET CBE20)
Description:
Sets the DHCP mode for the Communication Board Ethernet 20/25 (CBE20/CBE25).
Dependency:
Refer to: p8940, p8941, p8942, p8943, p8945
Notice:
When the DHCP mode is active (p8944 > 0), then PROFINET communication via this interface is no longer possible!
However, the interface can be used by the STARTER/SCOUT commissioning tool.
Note:
The active DHCP mode is displayed in parameter r8954.
The interface configuration (p8940 and following) is activated with p8945.
The parameter is not influenced by setting the factory setting.
If value = 0:
DHCP deactivated.
If value = 1:
Reserved.
If value = 2:
DHCP activated. The MAC address of this interface is used for client identification.
If value = 3:
DHCP activated. The station name of this interface is used for client identification.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0