TB30 analog inputs characteristic value y2 / TB30 AI char y2

TB30
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog inputs of Terminal Board 30 (TB30).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note:
The parameters for the characteristic do not have a limiting effect.
p4060[0...1]

TM31 analog inputs characteristic value y2 / TM31 AI char y2

TM31
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog inputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Notice:
This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note:
The parameters for the characteristic do not have a limiting effect.
p4061[0...1]

TM31 analog inputs wire breakage monitoring response threshold /

TM31 WireBrkThresh
TM31
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
0.00 [mA]
Description:
Sets the response threshold for wire-breakage monitoring of the analog inputs of Terminal Module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
For the following analog input type, the wire breakage monitoring is active:
p4056[x] = 3 (unipolar current input monitored (+4 mA ... +20 mA))
Refer to: r4056, p4056
p4062[0...1]
TM31 analog inputs wire breakage monitoring delay time / TM31 wirebrk t_del
TM31
Can be changed: U, T
Data type: Unsigned16
P-Group: Terminals
Not for motor type: -
Min
0 [ms]
Description:
Sets the delay time for wire-breakage monitoring of the analog inputs on Terminal Module 31 (TM31).
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1000.00 [%]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1000.00 [%]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
20.00 [mA]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1000 [ms]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 9104
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
Access level: 2
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
Access level: 2
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
2.00 [mA]
Access level: 2
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
100 [ms]