Encoder Type Oem Selection / Enc Type Oem Sel; Gearbox Type Selection / Gearbox Type Sel - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

For p0400 = 10000 the following applies:
If an identification is not possible, then p0400 is set to 0.
For p0400 = 10100 the following applies:
If an identification is not possible, p0400 remains set to 10100 until it becomes possible.
p0401[0...n]

Encoder type OEM selection / Enc type OEM sel

ENC, VECTOR_G
Can be changed: C2(1, 4)
Data type: Integer16
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Selects the encoder from the list of encoder types that the OEM supports.
Note:
The connected encoder can be identified by p0400 = 10000. This means that the encoder must support this and is
possible in the following cases: Motor with DRIVE-CLiQ, encoder with EnDat interface.
If an identification is not possible, then p0400 is set to 0.
The encoder data (e.g. pulse number p0408) can only be changed when p0400 = 9999.
Using p0400 = 20000, the encoder type can be selected from the list of OEM encoders using p0401.
p0402[0...n]

Gearbox type selection / Gearbox type sel

ENC, VECTOR_G
Can be changed: C2(1, 4)
Data type: Integer16
P-Group: Encoder
Not for motor type: -
Min
1
Description:
Selects the gearbox type to pre-set the inversion and the gearbox factor.
Measuring gear factor = motor or load revolutions / encoder revolutions.
Value:
1:
2:
3:
4:
9999: Gearbox user-defined
10000: Identify gearbox
10100: Identify gearbox
Dependency:
Refer to: p0410, p0432, p0433
Note:
Re p0402 = 1:
Automatic setting of p0410 = 0000 bin, p0432 = 1, p0433 = 1.
Re p0402 = 2:
Automatic setting of p0410 = 0011 bin, p0432 = 7, p0433 = 2.
Re p0402 = 3:
Automatic setting of p0410 = 0011 bin, p0432 = 17, p0433 = 4.
Re p0402 = 4:
Automatic setting of p0410 = 0011 bin, p0432 = 10, p0433 = 2.
Re p0402 = 9999:
No automatic setting of p0410, p0432, p0433. The parameters should be manually set.
Re p0402 = 10000:
It is only possible to identify the gearbox type for a motor with DRIVE-CLiQ. Parameters p0410, p0432 and p0433 are
set corresponding to the identified gearbox. If an identification is not possible, then p0402 is set to 9999.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Gearbox 1:1 not inverted
Gearbox 2:7 inverted
Gearbox 4:17 inverted
Gearbox 2:10 inverted
Calculated: -
Dyn. index: EDS, p0140
Units group: -
Scaling: -
Max
32767
Calculated: -
Dyn. index: EDS, p0140
Units group: -
Scaling: -
Max
10100
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 4700, 4704
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
9999
151

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130