2 Parameters
2.2 List of parameters
Note:
The numbers of the drive objects are in p0101.
Index 0:
Displays the number of drive objects that have already been set up.
Index 1:
Displays the number of drive objects that have already been set up and, in addition, the drive objects that still have to
be set up.
r0103

Application-specific view / Appl_spec view

B_INF, VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Closed-loop control
Not for motor type: -
Min
0
Description:
Displays the application-specific view of the individual drive object.
Dependency:
Refer to: p0107, r0107
p0103[0...n]
Application-specific view / Appl_spec view
CU_G130_DP,
Can be changed: C1(2)
CU_G130_PN,
Data type: Unsigned16
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
0
Description:
The application-specific view of an existing drive object is entered into each index.
The parameter cannot be changed.
Dependency:
Refer to: p0107, r0107
Note:
In the non-volatile memory, the application-specific views are defined in files with the following structure:
PDxxxyyy.ACX
xxx: Application-specific view (p0103)
yyy: Type of drive object (p0107)
Example:
PD052011.ACX
--> "011" stands for the drive object, type SERVO
--> "052" is the number of the view for this drive object
p0105

Activate/de-activate drive object / DO act/deact

B_INF, ENC, HUB,
Can be changed: T
TB30, TM150,
Data type: Integer16
VECTOR_G
P-Group: Closed-loop control
Not for motor type: -
Min
0
Description:
Setting to activate/de-activate a drive object.
Value:
0:
1:
2:
Recommend.:
After inserting all of the components of a drive object, before activating, first wait for Alarm A01316.
Dependency:
When activating drive objects with the safety functions enabled, the following applies:
After reactivating, a warm restart (p0009 = 30, p0976 = 2, 3) or POWER ON should be carried out.
Refer to: r0106
Notice:
The following applies when activating:
If components are inserted for the first time and the appropriate drive object is activated, then the drive system is
automatically booted. To do this, the pulses of all of the drive objects must be suppressed.
72
De-activate drive object
Activate drive object
Drive object de-activate and not present
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
999
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
2
List Manual (LH2), 04/2014, A5E03263479A
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1