Mot_Temp_Mod 3 Ambient Temperature Image P0613 / Ambtmp Image P0613 - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Bit field:
Bit
00
01
02
03
06
07
Dependency:
This parameter can only be changed if p5300=0 has been parameterized.
Refer to: p5300
Caution:
Please note the general conditions of the moment of inertia estimator, online tuning and adaptive resonance filter.
See Function Manual FH1.
Note:
Re bit 00: being prepared
The speed controller gain is determined and set using a noise signal.
Re bit 01: being prepared
Possibly required current setpoint filters are determined and set using a noise signal.
As a consequence, a higher dynamic performance can be achieved in the speed control loop.
Re bit 02:
Using this bit, the moment of inertia is determined while traversing (moment of inertia estimator). If this bit is not set,
then the load moment of inertia must be manually parameterized in parameter p1498.
Re bit 03:
If "once" has been parameterized, then after successfully determining the moment of inertia p1498 the moment of
inertia estimator is deactivated.
If "Cyclic" has been parameterized, then the moment of inertia is continually determined and the controller
parameters adapted. After the moment of inertia has been successfully determined (r1407.26=1), we recommend
that the parameter is saved. This means that after power on, the controller does not have to re-stabilize.
Re bit 06:
The adaptation of a current setpoint filter can be set here. See p5280-p5285.
This adaptation may be necessary if a mechanical resonance frequency changes in operation. It can also be used to
dampen a fixed resonance frequency. Once the control loop has stabilized, this bit should be deactivated and the
determined parameters saved in a non-volatile fashion.
Re bit 07:
With this function, these axes are adapted to the dynamic response set in p5275. This is necessary for interpolating
axes. The time in p5275 should be set according to the axis with the lowest dynamic response.
r5397

Mot_temp_mod 3 ambient temperature image p0613 / AmbTmp image p0613

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: ASM, REL, FEM
Min
- [°C]
Description:
Displays the ambient temperature for motor temperature model 3.
This value is used to calculate the utilization display (p0034).
The parameter value is an image of p0613.
Dependency:
Refer to: r0034
Note:
Users cannot see and change parameter p0613 (only Siemens internal).
692
Signal name
Setting Kp
Setting current setpoint filter
Moment of inertia estimator
Moment of inertia estimator
Current setpoint filter adaptation
Synchronized axes
1 signal
Yes
Yes
Yes
Cyclic
Yes
Yes
Calculated: -
Dyn. index: -
Units group: 21_1
Scaling: -
Max
- [°C]
List Manual (LH2), 04/2014, A5E03263479A
0 signal
No
No
No
Once
No
No
Access level: 2
Func. diagram: 8017
Unit selection: p0505
Expert list: 1
Factory setting
- [°C]
SINAMICS G130/G150
FP
-
-
-
-
-
-