Drive-Cliq Diagnostic Error Counter Connection / Dqdiag Err Counter; Drive-Cliq Diagnostic Configuration / Dq Diag Config; Drive-Cliq Detailed Diagnostics Configuration / Dq Diag Config - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

r9936[0...199]

DRIVE-CLiQ diagnostic error counter connection / DQdiag err counter

CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: Integer32
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
-
Description:
Displays the error counter for the individual DRIVE-CLiQ connections/cables.
r9936[0]: sum of the error counter for all connections
r9936[1]: not used
r9936[2]: error counter for the feeder cable to DRIVE-CLiQ components with component number 2
...
r9936[199]: error counter for the feeder cable to DRIVE-CLiQ components with component number 199
The feeder cable is the DRIVE-CLiQ cable that is connected to a component in the direction of the Control Unit.
Dependency:
Refer to: p9937, p9938
p9937

DRIVE-CLiQ diagnostic configuration / DQ diag config

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Unsigned16
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
-
Description:
Sets the configuration for the DRIVE-CLiQ diagnostics (error counter r9936).
Using this function, connections and cables of DRIVE-CLiQ connections can be checked for transfer errors. The error
counter is evaluated in the PHY blocks involved.
Bit field:
Bit
00
08
Dependency:
Refer to: r9936, p9938
Note:
Re bit 00:
To activate this function, p9938 must be set to 0 (inactive).
After changing the error counter (r9936), an appropriate alarm is output.
The alarm automatically disappears after 5 seconds.
Re bit 08:
With p9937.8 = 1, the error counters are reset (r9936[0...199]).
After the reset, p9937.8 is automatically set to 0.
p9938

DRIVE-CLiQ detailed diagnostics configuration / DQ diag config

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Integer16
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
0
Description:
Sets the configuration for the DRIVE-CLiQ detailed diagnostics (r9943).
Using the detailed diagnostics, it is possible to investigate data transfer errors on an individual connection, selected
using p9942.
Value:
0:
1:
2:
3:
4:
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Signal name
Alarm for connection error
Reset error counter
Inactive
Sum send and receive errors
Only send errors
Only receive errors
Siemens internal
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
6
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 0000 0000 0000 bin
0 signal
No
No
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
FP
-
-
957

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents