2 Parameters
2.2 List of parameters
p2101[0...19]
Change fault response response / Chng resp resp
CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Integer16
CU_G150_DP,
P-Group: Messages
CU_G150_PN, ENC,
Not for motor type: -
HUB, TB30, TM150,
TM31, TM54F_MA,
Min
TM54F_SL
0
Description:
Sets the fault response for the selected fault.
Value:
0:
Dependency:
The fault is selected and the required response is set under the same index.
Notice:
For the following cases, it is not possible to re-parameterize the fault response to a fault:
- Fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- Fault response is not permissible for the set fault number.
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
p2101[0...19]
Change fault response response / Chng resp resp
VECTOR_G
Can be changed: U, T
Data type: Integer16
P-Group: Messages
Not for motor type: -
Min
0
Description:
Sets the fault response for the selected fault.
Value:
0:
1:
2:
3:
5:
6:
7:
Dependency:
The fault is selected and the required response is set under the same index.
Refer to: p2100
Notice:
For the following cases, it is not possible to re-parameterize the fault response to a fault:
- Fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- Fault response is not permissible for the set fault number.
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The fault response can only be changed for faults with the appropriate identification (see the List Manual, chapter
"Faults and alarms").
Example:
F12345 and fault response = OFF3 (OFF1, OFF2, NONE)
--> The default fault response OFF3 can be changed to OFF1, OFF2 or NONE.
Re value = 1 (OFF1):
Braking along the ramp-function generator down ramp followed by a pulse inhibit.
Re value = 2 (OFF2):
Internal/external pulse inhibit.
Re value = 3 (OFF3):
Braking along the OFF3 down ramp followed by a pulse inhibit.
Re value = 5 (STOP2):
n_set = 0
502
NONE
NONE
OFF1
OFF2
OFF3
STOP2
Internal armature short-circuit / DC braking
ENCODER (p0491)
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
0
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
7
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 8050, 8075
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 8050, 8075
Unit selection: -
Expert list: 1
Factory setting
0