2 Parameters
2.2 List of parameters
27:
28:
29:
30:
31:
32:
Dependency:
Only the unit of the technology controller parameters are switched over (unit group 9_1).
Refer to: p0596
Note:
When switching over from % into another unit, the following sequence applies:
- set p0596
- set p0595 to the required unit
p0596

Technological unit reference quantity / Tech unit ref qty

VECTOR_G
Can be changed: T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.01
Description:
Sets the reference quantity for the technological units.
When changing over using changeover parameter p0595 to absolute units, all of the parameters involved refer to the
reference quantity.
Dependency:
Refer to: p0595
Notice:
When changing over from one technological unit into another, or when changing the reference parameter, a
changeover is not made.
p0600[0...n]

Motor temperature sensor for monitoring / Mot temp_sensor

VECTOR_G
Can be changed: C2(3), U, T
Data type: Integer16
P-Group: Motor
Not for motor type: -
Min
0
Description:
Sets the sensor to monitor the motor temperature.
The sensor type used is set in p0601.
Value:
0:
1:
2:
3:
10:
11:
20:
21:
Dependency:
Refer to: r0458, p0601, p0603
Caution:
If, for a selected temperature sensor (p0600 > 0), the motor temperature sensor is not connected but another sensor,
then the temperature adaptation of the motor resistances must be switched out. Otherwise, in controlled-loop
operation, torque errors will occur that will mean that the drive will not be able to be stopped.
Notice:
The parameter is calculated in the drive using p0340 and is inhibited for p0340 > 0.
For operation with a braking resistor (p1300 = 15), p0600 = 11 is automatically set when commissioning.
Note:
Re p0600 = 0:
With induction motors, the motor temperature is calculated using the motor temperature model (see also p0612.1).
Re p0600 = 1, 2, 3:
Bimetallic switch (p0601 = 4) and PT100 temperature sensor (p0601 = 5) are not supported.
Re p0600 = 10:
The BICO interconnection should be executed via connector input p0603.
216
inch³/h
lb/s
lb/min
lb/h
lbf
lbf ft
No sensor
Temperature sensor via encoder 1
Temperature sensor via encoder 2
Temperature sensor via encoder 3
Temperature sensor via a BICO interconnection
Temperature sensor via Motor Module / CU terminals
Temperature sensor via a BICO interconnection p0608
Temperature sensor via a BICO interconnection p0609
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
340.28235E36
Calculated: CALC_MOD_ALL
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
21
List Manual (LH2), 04/2014, A5E03263479A
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1.00
Access level: 2
Func. diagram: 8016
Unit selection: -
Expert list: 1
Factory setting
0