2 Parameters
2.2 List of parameters
p514[9]reference quantity 10
Up to 20 BiCos can be scaled to each of these 10 reference quantities.
Assignment parameters p515[0..19] up to p524[0..19] have been introduced for this purpose.
p0515[0...19]

Assignment parameter 1 in reference to p514[0] / BiCoList1_ref1

B_INF, VECTOR_G
Can be changed: T
Data type: Unsigned32
P-Group: Communications
Not for motor type: -
Min
0
Description:
Assignment parameter for user-specific scaling.
By indexing the assignment parameter p515[0..19], a total of 20 BiCos are available, which should be scaled
corresponding to the user-specific scaling.
The significance of the assignment parameters is as follows:
p515[0] BiCo number assigned p514[0] (reference quantity 01)
..
p515[19] BiCo number assigned p514[0] (reference quantity 01)
Dependency:
Refer to: p0514
p0516[0...19]

Assignment parameter 2 in reference to p514[1] / BiCoList2_ref2

B_INF, VECTOR_G
Can be changed: T
Data type: Unsigned32
P-Group: Communications
Not for motor type: -
Min
0
Description:
Assignment parameter for user-specific scaling.
By indexing the assignment parameter p516[0..19], a total of 20 BiCos are available, which should be scaled
corresponding to the user-specific scaling.
The significance of the assignment parameters is as follows:
p516[0] BiCo number assigned p514[1] (reference quantity 02)
..
p516[19] BiCo number assigned p514[1] (reference quantity 02)
Dependency:
Refer to: p0514
p0517[0...19]

Assignment parameter 3 in reference to p514[2] / BiCoList3_ref3

B_INF, VECTOR_G
Can be changed: T
Data type: Unsigned32
P-Group: Communications
Not for motor type: -
Min
0
Description:
Assignment parameter for user-specific scaling.
By indexing the assignment parameter p517[0..19], a total of 20 BiCos are available, which should be scaled
corresponding to the user-specific scaling.
208
Calculated: CALC_MOD_ALL
Dyn. index: -
Units group: -
Scaling: -
Max
4294967295
Calculated: CALC_MOD_ALL
Dyn. index: -
Units group: -
Scaling: -
Max
4294967295
Calculated: CALC_MOD_ALL
Dyn. index: -
Units group: -
Scaling: -
Max
4294967295
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0