Profibus Address / Pb Address; If1 Profidrive Pzd Telegram Selection / If1 Pzd Telegr - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

09
11
12
13
14
15
Note:
Re bits 00, 01, 02, 04, 05, 06, 09:
For PROFIdrive, these signals are used for status word 1.
Re bit 13:
When the "Safe Brake Control" (SBC) is activated and selected, the brake is no longer controlled using this signal.
Re bit 14, 15:
These signals are only of significance when the "extended brake control" function module is activated (r0108.14 = 1).
p0918

PROFIBUS address / PB address

CU_G130_DP,
Can be changed: T
CU_G150_DP
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
1
Description:
Displays or sets the PROFIBUS address for PROFIBUS interface on the Control Unit.
The address can be set as follows:
1) Using the address switch on the Control Unit.
--> p0918 can then only be read and displays the selected address.
--> A change only becomes effective after a POWER ON.
2) Using p0918
--> Only if the address 00 hex, 7F hex, 80 hex, or FF hex has been set using the address switch.
--> The address is saved in a non-volatile fashion using the function "copy from RAM to ROM".
--> A change only becomes effective after a POWER ON.
Note:
Permissible PROFIBUS addresses: 1 ... 126 (01 hex ... 7E hex)
Address 126 is used for commissioning.
Every PROFIBUS address change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
p0922

IF1 PROFIdrive PZD telegram selection / IF1 PZD telegr

B_INF
Can be changed: C2(1), T
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
370
Description:
Sets the send and receive telegram.
Value:
370:
371:
999:
Note:
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are
inhibited.
The inhibited interconnections can only be changed again after setting value 999.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Control request
Pulses enabled
Open holding brake
Command close holding brake
Pulse enable from the brake control
Setpoint enable from the brake control
SIEMENS telegram 370, PZD-1/1
SIEMENS telegram 371, PZD-5/8
Free telegram configuration with BICO
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
126
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
999
2 Parameters
2.2 List of parameters
No
No
No
No
No
No
Access level: 2
Func. diagram: 2401, 2410
Unit selection: -
Expert list: 1
Factory setting
126
Access level: 1
Func. diagram: 2401, 2420,
2423, 2447, 2457, 2481, 2483
Unit selection: -
Expert list: 1
Factory setting
999
-
-
-
-
-
-