2 Parameters
2.2 List of parameters
0: Firmware not yet checked.
1: Check running.
2: Check successfully completed.
3: Check indicates an error.
Dependency:
Refer to: r9925
p9930[0...8]

System logbook activation / SYSLOG activation

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Unsigned8
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
0
Description:
Only for service purposes.
Index:
[0] = System logbook stage (0: Not active)
[1] = COM2/COM1 (0: COM2, 1: COM1)
[2] = Activate file write (0: Not active)
[3] = Display time stamp (0: Not displayed)
[4...7] = Reserved
[8] = System logbook file size (stages, each 10 kB)
Notice:
Before powering down the Control Unit, ensure that the system logbook is switched out (p9930[0] = 0).
If writing to the file is activated (p9930[2] = 1), writing to the file must be de-activated again before switching off the
Control Unit (p9930[2] = 0) in order to ensure that the system logbook has been completely written to the file.
p9931[0...179]

System logbook module selection / SYSLOG mod select.

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Unsigned32
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
0000 hex
Description:
Only for service purposes.
p9932

Save system logbook EEPROM / SYSLOG EEPROM save

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Unsigned8
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
0
Description:
Only for service purposes.
r9935.0

BO: POWER ON delay signal / POWER ON t_delay

CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: Unsigned8
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
-
Description:
Display and binector output for a delay after POWER ON.
After power-on, binector output r9935.0 is set with the start of the first sampling time and is again reset after approx.
100 ms.
Bit field:
Bit
00
956
Signal name
POWER ON delay signal
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
FFFF FFFF hex
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
High
List Manual (LH2), 04/2014, A5E03263479A
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 hex
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Low
SINAMICS G130/G150
FP
-