r2705
CO: Reference angle / Reference angle
B_INF, VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Connector output of the reference quantity for angles p2005.
All angles specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
This parameter has the unit degree.
Dependency:
Refer to: p2005
Note:
This BICO parameter provides the numerical value of the reference quantity p2005 as a connector output for
interconnection with Drive Control Chart (DCC). The numerical value can be adopted unchanged from this connector
output in DCC. This BICO parameter is not suitable for interconnecting for cyclic communication.
r2706
CO: Reference temp / Reference temp
B_INF, TM150, TM31,
Can be changed: -
VECTOR_G
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Connector output of the reference quantity for temperatures.
All temperatures specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
This parameter has the unit degree Celsius.
Note:
This BICO parameter provides the numerical value of the reference quantity for the temperature as a connector
output for interconnection with Drive Control Chart (DCC). The numerical value can be adopted unchanged from this
connector output in DCC. This BICO parameter is not suitable for interconnecting for cyclic communication.
r2707
CO: Reference acceleration / Ref accel
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Connector output of the reference quantity for accelerations p2007.
All acceleration rates specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
The unit of this parameter is the same as the unit selected for p2007.
Dependency:
r0108.12, p0505
Refer to: p2007
Note:
This BICO parameter provides the numerical value of the reference quantity p2007 as a connector output for
interconnection with Drive Control Chart (DCC). The numerical value in the currently selected unit can be adopted
unchanged from this connector output in DCC. This BICO parameter is not suitable for interconnecting for cyclic
communication.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
547