Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
26
29
Dependency:
Refer to: r0002
Note:
The value r0046 = 0 indicates that all enable signals for the infeed are present.
Bit 00 = 1 (enable signal missing), if:
- the signal source in p0840 is a 0 signal.
- there is a "switching on inhibited".
Bit 01 = 1 (enable signal missing), if:
- the signal source in p0844 or p0845 is a 0 signal.
Bit 16 = 1 (enable signal missing), if:
- there is an OFF1 fault response. The system is only enabled if the fault is removed and was acknowledged and the
"switching on inhibited" withdrawn with OFF1 = 0.
Bit 17 = 1 (enable signal missing), if:
- the commissioning mode is selected (p0009 > 0 or p0010 > 0) or there is an OFF2 fault response or the OFF1
signal source (p0840) is changed.
Bit 26 = 1 (enable signal missing), if:
- the infeed is inactive (p0105 = 0) or is not operational (r7850[DO-Index]=0).
Bit 29 = 1 (enable signal missing), if:
- the cooling unit ready signal via binector input p0266[1] missing.
r0046.0...31
CO/BO: Missing enable sig / Missing enable sig
VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Display and BICO output for missing enable signals that are preventing the closed-loop drive control from being
commissioned.
Bit field:
Bit
00
01
02
03
04
05
08
09
10
11
12
15
16
17
18
19
20
21
25
26
27
28
29
30
31
Dependency:
Refer to: r0002
56
Infeed inactive or not operational
Cooling unit ready signal missing
Signal name
OFF1 enable missing
OFF2 enable missing
OFF3 enable missing
Operation enable missing
Armature short-circuit / DC braking enable
missing
STOP2 enable missing
Safety enable missing
Infeed enable missing
Ramp-function generator enable missing
Ramp-function generator start missing
Setpoint enable missing
QuickStop enable missing
OFF1 enable internal missing
OFF2 enable internal missing
OFF3 enable internal missing
Pulse enable internal missing
Armature short-circuit/DC braking internal
enable missing
STOP2 enable internal missing
Function bypass active
Drive inactive or not operational
De-magnetizing not completed
Brake open missing
Cooling unit ready signal missing
Speed controller inhibited
Jog setpoint active
Yes
Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
List Manual (LH2), 04/2014, A5E03263479A
No
No
Access level: 1
Func. diagram: 2634
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
SINAMICS G130/G150
-
-
FP
7954
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-