2 Parameters
2.2 List of parameters
136 / 136xx, 146xx, 156xx
166 / 166xx, 176xx, 186xx
264 / 264xx, 274xx, 284xx, 294xx
283 / 283xx, 293xx
For 1PQ8 motors (p0300 = 18) the fan type p0335 should be set to 5.
Note:
With p0300 = 10000, for a motor with DRIVE-CLiQ, the motor parameters are automatically downloaded, with p0300
= 10001, the motor parameters of a second data set (if available).
If a motor type has not been selected (p0300 = 0), then the drive commissioning routine cannot be exited.
A motor type with a value above p0300 >= 100 describes motors for which a motor parameter list exists.
Motor types with a value below p0300 < 100 correspond to the selection of a third-party motor. When appropriately
selected, this means that the motor parameters are pre-assigned the settings for a third-party motor.
This also applies for parameters for a motor with DRIVE-CLiQ. In this case p0300 can only be set to p0300 = 10000
or 10001 (read motor parameters) or to the corresponding non-Siemens motor (first digit of the motor code number)
in order to be able to cancel the write protection.
p0301[0...n]

Motor code number selection / Mot code No. sel

VECTOR_G
Can be changed: C2(1, 3)
Data type: Unsigned16
P-Group: Motor
Not for motor type: FEM
Min
0
Description:
The parameter is used to select a motor from a motor parameter list.
When changing the code number (with the exception to the value 0), all of the motor parameters are pre-assigned
from the internally available parameter lists.
Dependency:
Code numbers can only be selected for motor types that correspond to the motor type selected in p0300. For 1PH2,
1PH4, 1PH7, 1PM4, 1PM6, 1FT6 motors, code numbers are also possible, whose fourth decimal position is greater
by a value of 1 or 2 than the matching motor type in p0300. For 1FE1 motors, the third decimal position can be higher
by a value of 1.
Refer to: p0300
Note:
The motor code number can only be changed if the matching catalog motor was first selected in p0300.
For a motor with DRIVE-CLiQ, p0301 cannot be changed. In this case, p0301 is automatically written to the code
number of the motor parameter read in (r0302) if p0300 is set to 10000.
When selecting a catalog motor (p0300 >= 100), drive commissioning can only be exited if a code number is
selected.
r0302[0...n]

Motor code number of motor with DRIVE-CLiQ / Mot code mot w/ DQ

VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Motor
Not for motor type: -
Min
-
Description:
Displays the motor code number from the saved motor data from a motor with DRIVE-CLiQ.
Note:
Drive commissioning can only be exited if the code number that was downloaded (r0302) matches the stored code
number (p0301). If the numbers differ, then the motor data set should be re-loaded using p0300 = 10000.
The motor data are always expected from the first encoder that is assigned to the drive data sets (refer to p0187 =
encoder 1) data set number.
The value is not updated cyclically but only on specific events (e.g. update DRIVE-CLiQ device).
r0302 = 0: No motor with DRIVE-CLiQ found
120
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents