2 Parameters
2.2 List of parameters
p9552
SI Motion transition time STOP C to SOS (SBH) (Control Unit) / SI Mtn t C->SOS CU
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the transition time from STOP C to "Safe Operating Stop" (SOS).
Note:
The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
SOS: Safe Operating Stop / SBH: Safe operating stop
p9553
SI Motion transition time STOP D to SOS (SBH) (Control Unit) / SI Mtn t D->SOS CU
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the transition time from STOP D to "Safe Operating Stop" (SOS).
Note:
The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
SOS: Safe Operating Stop / SBH: Safe operating stop
p9554
SI Motion transition time STOP E to SOS (SBH) (Control Unit) / SI Mtn t E->SOS CU
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the transition time from STOP E to "Safe Operating Stop" (SOS).
Dependency:
Refer to: p9354
Note:
The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
SOS: Safe Operating Stop / SBH: Safe operating stop
p9555
SI Motion transition time STOP F to STOP B (Control Unit) / SI Mtn t F->B CU
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the transition time from STOP F to STOP B.
Note:
The set time is rounded internally to an integer multiple of the monitoring clock (p9500/p9300) cycle.
892
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
600000.00 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
600000.00 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
600000.00 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
600000.00 [ms]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 2819
Unit selection: -
Expert list: 1
Factory setting
100.00 [ms]
Access level: 3
Func. diagram: 2819
Unit selection: -
Expert list: 1
Factory setting
100.00 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100.00 [ms]
Access level: 3
Func. diagram: 2819
Unit selection: -
Expert list: 1
Factory setting