Re bit 04:
When sensing the velocity without encoder, a distinction is made between the closed-loop speed controlled and
open-loop speed controlled (U/f) modes.
Re bit 09:
Safe pulse pulse cancellation is a state that can only occur for the combination of velocity sensing without encoder
(p9506) and drive-integrated motion monitoring functions without selection (p9601.5). In this state, internally an STO
is initiated, which can be withdrawn again using an OFF1 enable.
Re bit 12:
An active test stop is also displayed using the safety message C01798.
ESR: Extended Stop and Retract
SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SBR: Safe Brake Ramp (safe brake ramp monitoring)
r9724

SI Motion crosswise comparison clock cycle / SI Mtn CDC clk cyc

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
- [ms]
Description:
Displays the crosswise comparison clock cycle.
The value indicates the clock cycle time with which each individual CDC value is compared between the two
monitoring channels.
Dependency:
Refer to: p9500
Note:
Crosswise comparison clock cycle = monitoring clock cycle (p9500) * number of data to be crosswise compared
CDC: Crosswise Data Comparison
r9725[0...2]

SI Motion diagnostics STOP F / SI Mtn Diag STOP F

VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Re index 0:
Displays the message value that resulted in the STOP F on the drive.
Value = 0:
The Control Unit signaled a STOP F.
Value = 1 ... 999:
Number of the incorrect date in the crosswise data comparison between the monitoring channels.
Value >= 1000:
Additional diagnostic values of the drive.
Re index 1:
Displays the value of the Control Unit that resulted in the STOP F.
Re index 2:
Displays the value from the second channel that resulted in the STOP F.
Index:
[0] = Message value for CDC
[1] = Control Unit CDC actual value
[2] = Components CDC actual value
Note:
The significance of the individual message values is described in message C01711.
CDC: Crosswise Data Comparison
Re Index 1, 2:
When Safety message C01711 with message value >= 1000 occurs, these indices are not supplied with values.
920
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
- [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-