Bi: Sync-Line-Drive Enable / Sync Enable; Co/Bo: Sync-Line-Drive Control Word / Sync Stw; Co: Sync-Line-Drive Target Frequency / Sync F_Target; Co: Sync-Line-Drive Frequency Difference / Sync F_Diff - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p3802[0...n]

BI: Sync-line-drive enable / Sync enable

VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Functions
Not for motor type: -
Min
-
Description:
Sets the signal source to switch in/switch out for the line-drive synchronization.
BI: p3802 = 1 signal:
The line-drive synchronization is switched in.
Dependency:
Refer to: p3800, p3801
r3803.0

CO/BO: Sync-line-drive control word / Sync STW

VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Functions
Not for motor type: -
Min
-
Description:
Displays the control word for the line-drive synchronization.
Bit field:
Bit
00
Note:
Re bit 00:
For a 1 signal, p3800 > 0 is set.
r3804

CO: Sync-line-drive target frequency / Sync f_target

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
- [Hz]
Description:
Displays the target frequency for the line-drive synchronization.
r3805

CO: Sync-line-drive frequency difference / Sync f_diff

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
- [Hz]
Description:
Displays the frequency difference between the measured target frequency and output frequency of the gating unit of
the closed-loop control for line-drive synchronization.
578
Signal name
Sync-line-drive selected
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: p2000
Max
- [Hz]
Calculated: -
Dyn. index: -
Units group: -
Scaling: p2000
Max
- [Hz]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 2
Func. diagram: 7020
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
Access level: 2
Func. diagram: 3030, 7020
Unit selection: -
Expert list: 1
Factory setting
- [Hz]
Access level: 2
Func. diagram: 7020
Unit selection: -
Expert list: 1
Factory setting
- [Hz]
SINAMICS G130/G150
FP
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents