r1114

CO: Setpoint after the direction limiting / Setp after limit

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
- [rpm]
Description:
Displays the speed/velocity setpoint after the changeover and limiting the direction.
p1115

Ramp-function generator selection / RFG selection

VECTOR_G
Can be changed: T
Data type: Integer16
P-Group: Setpoints
Not for motor type: -
Min
0
Description:
Sets the ramp-function generator type.
Value:
0:
1:
Note:
Another ramp-function generator type can only be selected when the motor is at a standstill.
r1119

CO: Ramp-function generator setpoint at the input / RFG setp at inp

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
- [rpm]
Description:
Displays the setpoint at the input of the ramp-function generator.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
The setpoint is influenced by other functions, e.g. skip (suppressed) speeds, minimum and maximum limits.
p1120[0...n]

Ramp-function generator ramp-up time / RFG ramp-up time

VECTOR_G
Can be changed: C2(1), U, T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
0.000 [s]
Description:
The ramp-function generator ramps-up the speed setpoint from standstill (setpoint = 0) up to the maximum speed
(p1082) in this time.
Dependency:
Refer to: p1082, p1138
Note:
The ramp-up time can be scaled via connector input p1138.
The parameter is adapted during the rotating measurement (p1960 > 0). This is the reason that during the rotating
measurement, the motor can accelerate faster than was originally parameterized.
For U/f control and sensorless vector control (see p1300), a ramp-up time of 0 s is not expedient. The setting should
be based on the startup times (r0345) of the motor.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Basic ramp-function generator
Extended ramp-function generator
Calculated: -
Dyn. index: -
Units group: 3_1
Scaling: p2000
Max
- [rpm]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Units group: 3_1
Scaling: p2000
Max
- [rpm]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
999999.000 [s]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 3001, 3040,
3050
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]
Access level: 3
Func. diagram: 3001, 3080
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 3001, 3050,
3060, 3070, 6300
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]
Access level: 1
Func. diagram: 3060, 3070
Unit selection: -
Expert list: 1
Factory setting
10.000 [s]