r0036

CO: Power unit overload I2t / PU overload I2t

B_INF, VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [%]
Description:
Displays the power unit overload determined using the I2t calculation.
A current reference value is defined for the I2t monitoring of the power unit. It represents the current that can be
conducted by the power unit without any influence of the switching losses (e.g. the continuously permissible current
of the capacitors, inductances, busbars, etc.).
If the I2t reference current of the power unit is not exceeded, then an overload (0 %) is not displayed.
In the other case, the degree of thermal overload is calculated, whereby 100% results in a trip.
Dependency:
Refer to: p0290, p0294
r0037[0...19]

CO: Power unit temperatures / PU temperatures

B_INF, VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [°C]
Description:
Display and connector output for the temperature in the power unit.
Index:
[0] = Inverter maximum value
[1] = Depletion layer maximum value
[2] = Rectifier maximum value
[3] = Air intake
[4] = Interior of power unit
[5] = Inverter 1
[6] = Inverter 2
[7] = Inverter 3
[8] = Inverter 4
[9] = Inverter 5
[10] = Inverter 6
[11] = Rectifier 1
[12] = Rectifier 2
[13] = Depletion layer 1
[14] = Depletion layer 2
[15] = Depletion layer 3
[16] = Depletion layer 4
[17] = Depletion layer 5
[18] = Depletion layer 6
[19] = Cooling unit liquid intake
Notice:
Only for internal Siemens troubleshooting.
Note:
The value of -200 indicates that there is no measuring signal.
r0037[0]: Maximum value of the inverter temperatures (r0037[5...10]).
r0037[1]: Maximum value of the depletion layer temperatures (r0037[13...18]).
r0037[2]: Maximum value of the rectifier temperatures (r0037[11...12]).
The maximum value is the temperature of the hottest inverter, depletion layer, or rectifier.
In the case of a fault, the particular shutdown threshold depends on the power unit, and cannot be read out.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: PERCENT
Max
- [%]
Calculated: -
Dyn. index: -
Units group: 21_1
Scaling: p2006
Max
- [°C]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8014
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: 8014
Unit selection: p0505
Expert list: 1
Factory setting
- [°C]
53