2 Parameters
2.2 List of parameters
p1268
BI: Bypass feedback synchronization completed / FS sync compl
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the feedback signal "synchronization completed" for the bypass function.
Dependency:
Refer to: r3819
p1269[0...1]
BI: Bypass switch feedback signal / Bypass FS
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the feedback signal of the bypass switch.
Index:
[0] = Switch motor/drive
[1] = Switch motor/line supply
Note:
In the case of switches without a feedback signal, interconnect the corresponding control bit as the signal source:
BI: p1269[0] = r1261.0
BI: p1269[1] = r1261.1
p1271[0...n]
Flying restart maximum frequency for the inhibited direction / FlyRes f_max dir
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0 [Hz]
Description:
Sets the maximum search frequency for a flying restart in an inhibited setpoint direction (p1110, p1111).
Note:
The parameter has no effect for an operating mode, which only searches in the setpoint direction (p1200 > 3).
p1272
Simulation mode / Simulation mode
VECTOR_G
Can be changed: T
Data type: Integer16
P-Group: Functions
Not for motor type: -
Min
0
Description:
In the simulation mode, the closed-loop control or U/f control can be operated without motor.
The simulation mode is used to test the power unit. Even though the DC link voltage is missing, the pulses are
enabled when powering up. The DC link pre-charging is bypassed and the undervoltage detection is disabled.
Closed-loop speed control with an encoder is possible if the torque setpoint (r0079) is used in order to operate a
second drive in the closed-loop torque controlled mode.
Value:
0:
1:
Dependency:
The following functions are de-activated in the simulation mode:
- motor data identification routine
- motor data identification routine, rotating without encoder
- pole position identification
340
OFF
ON
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
650 [Hz]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
3819.2
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0 [Hz]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150