Co/Bo: Excitation Status Word / Excitation Zsw; Current Setpoint Torque-Generating Before Filter / Iq_Set Before Filt; Co: Torque Setpoint Function Generator / M_Set Fg; Current Setpoint Torque-Generating Smoothing Time Minimum - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
r1649.0...8

CO/BO: Excitation status word / Excitation ZSW

VECTOR_G (n/M)
Can be changed: -
Data type: Unsigned16
P-Group: Displays, signals
Not for motor type: ASM, PEM, REL
Min
-
Description:
Displays the status word of the excitation equipment.
Bit field:
Bit
00
01
02
03
07
08
Dependency:
Refer to: p1645
r1650

Current setpoint torque-generating before filter / Iq_set before filt

VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
- [Arms]
Description:
Displays the torque generating current setpoint Iqset after the torque limits and the clock cycle interpolation is ahead
of the current setpoint filters.
r1651

CO: Torque setpoint function generator / M_set FG

VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
- [Nm]
Description:
Displays the torque setpoint of the function generator.
p1653[0...n]
Current setpoint torque-generating smoothing time minimum / Isq_s T_smth min
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: PEM, REL
Min
0.1 [ms]
Description:
Sets the minimum smoothing time constant for the setpoint of the torque-generating current components.
406
Signal name
Excitation ready to be powered up feedback
signal
Excitation ready feedback signal
Excitation operational feedback signal
Excitation group signal fault
Excitation group signal alarm
Excitation at the voltage limit
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Units group: 6_2
Scaling: p2002
Max
- [Arms]
Calculated: -
Dyn. index: -
Units group: 7_1
Scaling: p2003
Max
- [Nm]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
20.0 [ms]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 2
Func. diagram: 6495
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
Access level: 3
Func. diagram: 5710
Unit selection: p0505
Expert list: 1
Factory setting
- [Arms]
Access level: 3
Func. diagram: -
Unit selection: p0505
Expert list: 1
Factory setting
- [Nm]
Access level: 4
Func. diagram: 6710
Unit selection: -
Expert list: 1
Factory setting