r2231
Technology controller motorized potentiometer setpoint memory / Tec_ctrl mop mem
VECTOR_G
Can be changed: -
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
- [%]
Description:
Displays the setpoint memory for the motorized potentiometer of the technology controller.
For p2230.0 = 1, the last setpoint that was saved is entered after ON.
Dependency:
Refer to: p2230
p2235[0...n]
BI: Technology controller motorized potentiometer raise setpoint / Tec_ctrl mop raise
VECTOR_G
Can be changed: T
(Tech_ctrl)
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source to continually increase the setpoint for the motorized potentiometer of the technology
controller.
The setpoint change (CO: r2250) depends on the set ramp-up time (p2247) and the duration of the signal that is
present (BI: p2235).
Dependency:
Refer to: p2236
p2236[0...n]

BI: Technology controller motorized potentiometer lower setpoint /

Tec_ctrl mop lower
VECTOR_G
Can be changed: T
(Tech_ctrl)
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source to continually reduce the setpoint for the motorized potentiometer of the technology controller.
The setpoint change (CO: r2250) depends on the set ramp-down time (p2248) and the duration of the signal that is
present (BI: p2236).
Dependency:
Refer to: p2235
p2237[0...n]
Technology controller motorized potentiometer maximum value / Tec_ctrl mop max
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-200.00 [%]
Description:
Sets the maximum value for the motorized potentiometer of the technology controller.
Dependency:
Refer to: p2238
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: 9_1
Scaling: -
Max
- [%]
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: DDS, p0180
Units group: 9_1
Scaling: -
Max
200.00 [%]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 7954
Unit selection: p0595
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: 7954
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 7954
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 7954
Unit selection: p0595
Expert list: 1
Factory setting
100.00 [%]