p0316[0...n]

Motor torque constant / Mot kT

VECTOR_G
Can be changed: C2(1, 3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, REL, FEM
Min
0.00 [Nm/A]
Description:
Sets the torque constant of the synchronous motor.
p0316 = 0:
The torque constant is calculated from the motor data.
p0316 > 0:
The selected value is used as torque constant.
Dependency:
Refer to: r0334
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
This parameter is not used for induction motors (p0300 = 1xx).
p0318[0...n]

Motor stall current / Mot I_standstill

VECTOR_G
Can be changed: C2(3)
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, REL, FEM
Min
0.00 [Arms]
Description:
Sets the stall current for synchronous motors (p0300 = 2xx).
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The parameter is used for the I2t monitoring of the motor (refer to p0611).
This parameter is not used for induction motors (p0300 = 1xx).
p0320[0...n]
Motor rated magnetizing current/short-circuit current / Mot I_mag_rated
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: REL, FEM
Min
0.000 [Arms]
Description:
Induction motors:
Sets the rated motor magnetizing current.
For p0320 = 0.000 the magnetizing current is internally calculated and displayed in r0331.
Synchronous motors:
Sets the rated motor short-circuit current.
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The magnetization current p0320 for induction motors (not for catalog motors) is reset when quick commissioning is
exited with p3900 > 0.
VECTOR:
If, for induction motors, the magnetizing current p0320 is changed outside the commissioning phase (p0010 > 0),
then the magnetizing inductance p0360 is changed so that the EMF r0337 remains constant.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: MDS, p0130
Units group: 28_1
Scaling: -
Max
400.00 [Nm/A]
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
10000.00 [Arms]
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
5000.000 [Arms]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: -
Unit selection: p0100
Expert list: 1
Factory setting
0.00 [Nm/A]
Access level: 3
Func. diagram: 8017
Unit selection: -
Expert list: 1
Factory setting
0.00 [Arms]
Access level: 3
Func. diagram: 5722
Unit selection: -
Expert list: 1
Factory setting
0.000 [Arms]
125