p3322[0...n]

Fluid flow machine power point 2 / Fluid_mach P2

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the power (P) of point 2 as a [%].
Dependency:
Refer to: r0041, p3320, p3321, p3323, p3324, p3325, p3326, p3327, p3328, p3329
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3323[0...n]

Fluid flow machine speed point 2 / Fluid_mach n2

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 2 as a [%].
Dependency:
Refer to: r0041, p3320, p3321, p3322, p3324, p3325, p3326, p3327, p3328, p3329
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3324[0...n]

Fluid flow machine power point 3 / Fluid_mach P3

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the power (P) of point 3 as a [%].
Dependency:
Refer to: r0041, p3320, p3321, p3322, p3323, p3325, p3326, p3327, p3328, p3329
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3325[0...n]

Fluid flow machine speed point 3 / Fluid_mach n3

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 3 as a [%].
Dependency:
Refer to: r0041, p3320, p3321, p3322, p3323, p3324, p3326, p3327, p3328, p3329
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
100.00
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
100.00
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
100.00
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
100.00
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
50.00
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
25.00
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
77.00
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
50.00