6.3
2 - 30
KWh @ AC Input I x 120V/1000: Base chassis=0.324 KWh,
Expansion chassis=0.324 KWh, total 1.296 KWh
BTU (KWh x 3413): Base chassis=
chassis=
1106 BTU
Double Pole/Neutral Fusing
(power supply fuses are located at both the L and N
side).
Dedicated 120 Vac
60 Hz circuit located within seven feet of the chassis
Dedicated 15A circuit
Single Phase
A dedicated outlet, separately fused and grounded for each chassis
should be installed
Double Pole/Neutral Fusing
(power supply fuses are located at both the L and N
side).
6.2.2

Power Supply Consumption

Chassis
Basic Chassis – CD-CP00-US Chassis
Basic Chassis + Expansion Chassis
Basic Chassis + 2 Expansion Chassis
Basic Chassis + 3 Expansion Chassis

Environmental Conditions

6.3.1

Temperature and Humidity

Chassis, Telephones, 16LK, Console, ADA, APR
Operating Temperature: +32°F ~ +104°F (0°C ~ 40°C)
Recommended Long Term Temperature: -4°F ~ +140°F (-20°C ~
60°C)
1106 BTU
, total
4424 BTU

Table 2-17 Power Consumption

Maximum
RMS
Current
2.7 A
5.4 A
8.1 A
10.8 A
UNIVERGE SV8100/SV8300
, Expansion
Watts Used
Watts Used
(Idle)
(Maximum)
180
120
240
360
480
720
SV8100 System Specifications
360
540