Download Print this page

Toshiba GR-200 Series Instruction Manual page 968

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

1.
Introduction
This model implementation conformance statement is applicable for GRE200 with firmware
G2M850-02-A:
This MICS document specifies the modeling extensions compared to IEC 61850 Edition 2. For
the exact details on the standardized model please compare the ICD substation configuration
file: "<T2GRE200xxxx.icd>", version <D000>.
(† xxxx is version)
Clause 2 contains the list of implemented logical nodes.
<Note: remove the non-applicable clause>
2.
Logical Nodes List
The following table contains the list of logical nodes implemented in the device:
The logical nodes of GR series are configurable and this is default setting information.
L: System Logical Nodes
P: Logical Nodes for Protection functions
R: Logical Nodes for protection related functions
G: Logical Nodes for Generic references
M: Logical Nodes for Metering and measurement
LPHD (Physical device information)
LLN0 (Logical node zero)
LGOS (GOOSE Subscription)
PDUP (Directional underpower)
PFRC (Rate of change of frequency)
PHAR (Harmonic restraint)
PSCH (Protection scheme)
PTOC (Time overcurrent)
PTOF (Overfrequency)
PTOV (Overvoltage)
PTRC (Protection trip conditioning)
PTTR (Thermal overload)
PTUC (Undercurrent)
PTUF (Underfrequency)
PTUV (Undervoltage)
RBRF (Breaker failure)
RFLO (Fault locator)
RREC (Autoreclosing)
RSYN (Synchronism-check)
GGIO (Generic process I/O)
MMXU (Measurement)
MSQI (Sequence and imbalance)
- 949 -
6F2T0200 (0.15)
(MICS Ed.2)
GRE200 (1,2)

Advertisement