Toshiba GR-200 Series Instruction Manual page 476

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Note: To identify the input and output signal-points in the other DPOS logics, see Table
††
4.1-13 for PLC#1, Table 4.1-14 for PLC#2, Table 4.1-17 and Table 4.1-19 for output
signals.
Note: The "Operate failed" signal is issued when a state-change remains undetected
‡‡
following expiration of the setting to timer [DPOS01-RST].
Receiving "Operate command Off" using PLC function
(vi)
Figure 4.1-29 outlines the reception of the operate command 'Off ' by the PLC function.
Wait for a command
Select stage
Select command On from the remote-end
Select command Off from the remote-end
Select command On from the local-end
Select command Off from the local-end
Select command On by the PLC
Select command Off by the PLC
Figure 4.1-29 Outline of Operate command 'Off'
Input signal from the PLC function
Figure 4.1-30 depicts the operate logic when an "Operate command Off (PLC-Off-control)"
signal is generated by the PLC function. There are two input points for reception of this
command signal, like the signal "Operate command On (PLC-On-control)", That is, if an
interlock check is required, apply the signal at connection point (PLC#3: i.e.
DEV01_OP_INTERLOCK). If, on the other hand an interlock check is not required, apply the
signal at the other connection point (PLC#4: i.e. DEV01_OP_COMMAND). PLC#3 and PLC#4
are denoted as PLC#1 and PLC#2 in Table 4.1-2.
Output signal to BO
The DPOS01 function, in Figure 4.1-30, can issue an "Operate" signal at output-point
"DPOS01_FEX_BO", when the DPOS01 function determines that the signal "PLC-Off-Control"
is true.
Wait for a next command
Operate command On from the remote-end
Operate command Off from the remote-end
Operate command On from the local-end
Operate command Off from the local-end
Operate command On by the PLC
Operate command Off by the PLC
Operate logic
PLC logic programmed
by the user l
- 457 -
6F2T0200 (0.15)
Success
Operation
Signal output
decision
Do nothing
Failed
GRE200 (1,2)