Setting
2.26.5
FL-Z_MV (Function ID: 495081) at Common
Setting items
FL_EN
FL_Dir
FL_ImpSet
Matrix
FL_Xaa
FL_Xbb
FL_Xcc
FL_Xab
FL_Xbc
FL_Xca
FL_Raa
FL_Rbb
FL_Rcc
FL_Rab
FL_Rbc
FL_Rca
Symme
FL_X1
trical
FL_R1
FL_X0
FL_R0
FL_Kab
FL_Kbc
FL_Kca
FL_Ka
FL_Kb
FL_Kc
FL_Unit
Unit
FL_Line_km
FL_Line_mile
FL_AllZone
Range
Unit
Off / On
- Fault locator enable
Forward / Reverse
- Metering direction
Symmetrical / Matrix
- Selection in the setting mode of impedance
0.00 - 1000.00
- Reactance component of line (Xaa)
0.00 - 1000.00
- Reactance component of line (Xbb)
0.00 - 1000.00
- Reactance component of line (Xcc)
0.00 - 1000.00
- Reactance component of line (Xab)
0.00 - 1000.00
- Reactance component of line (Xbc)
0.00 - 1000.00
- Reactance component of line (Xac)
0.00 - 1000.00
- Resistance component of line (Raa)
0.00 - 1000.00
- Resistance component of line (Rbb)
0.00 - 1000.00
- Resistance component of line (Rcc)
0.00 - 1000.00
- Resistance component of line (Rab)
0.00 - 1000.00
- Resistance component of line (Rbc)
0.00 - 1000.00
- Resistance component of line (Rac)
Reactance component of line positive sequence
0.00 - 1000.00
-
impedance
Resistance
0.00 - 1000.00
-
sequence impedance
Reactance component of line zero sequence
0.00 - 1000.00
-
impedance
Resistance component of line zero sequence
0.00 - 1000.00
-
impedance
50 - 150
% Impedance imbalance compensation factors
50 - 150
% Impedance imbalance compensation factors
50 - 150
% Impedance imbalance compensation factors
50 - 150
% Impedance imbalance compensation factors
50 - 150
% Impedance imbalance compensation factors
50 - 150
% Impedance imbalance compensation factors
km / mile
- Selection of line length unit
0.0 - 500.0
km Line length (km)
mil
0.0 - 310.0
Line length (mile)
es
Off / On
- Display the outside of the boundary
- 306 -
Contents
component
of
line
positive
6F2T0200 (0.15)
Default
Note
On
Forward
Symmetrical
10.50
10.50
10.50
0.50
0.50
0.50
1.10
1.10
1.10
0.10
0.10
0.10
10.00
1.00
34.00
3.50
100
100
100
100
100
100
km
50.0
31.0
Off