Setting for "Select command On"
For example, the point "DPOS01_OSL_BO_FLG" is connected to the BO1 circuit for the issuing
of the command; the user can connect point "BO1-RB" with the contact health check function
using the setting [DPOS01-OSLBORD]. Do not key the point "DPOS01_OSL_BO_FLG".
Selecte logic in
DPOS01
" DPOS01_OSL_BO_FLG "
(512001 8603011DC6)
BO1 circuit at
(200B41_8002001113)
Figure 4.1-45 Example connection of "Select command On" for the health check feature
Setting for "Select command Off"
Similar to "select command On", the point "DPOS01_FSL_BO_FLG" is connected with the BO2
circuit; the user is required to key point "BO2-RB" for the setting [DPOS01-FSLBORD]. Do not
key the point "DPOS01_FSL_BO_FLG".
Selection logic in
DPOS01
" DPOS01_FSL_BO_FLG "
(55120018 A03011DC4)
BO1 circuit at
(200B41_8102001113)
Figure 4.1-46 Example connection of "Select command Off" for the health check feature
IO#1-2
" BO1-RB "
Signal connected by
setting [DPOS01-OSLBORD]
Connection made by the user
IO#1-2
" BO2-RB "
Signal connected by
setting [DPOS01-FSLBORD]
Connection made by the user
- 475 -
Contact health check
logic in DPOS01
&
Result of contact health check
Contact health check
logic in DPOS01
Result of contact health check
&
6F2T0200 (0.15)
GRE200 (1,2)